Retrofitting an RCD: obligations and practice

Technically reviewed by Reinlicht Elektrotechnik, as of 31 October 2026

The short answer

There is no general obligation to retrofit older installations in private homes with a residual current device (RCD, German: FI-Schutzschalter). An RCD must be added in the event of alterations, extensions, a change of use or an evident hazard. In new installations, a 30 mA RCD is mandatory for socket outlets up to 32 A and for lighting in dwellings.

What does an RCD do?

An RCD disconnects a circuit as soon as current flows to earth along an unintended path, for example via the protective earth conductor or through a person. In German it is commonly called a FI-Schutzschalter; the technical term is residual current device, RCD for short. It works by comparing the current flowing to an appliance with the current flowing back.

For protection of persons, an RCD with a rated residual operating current of no more than 30 mA is used. For comparison: according to TÜV Hessen, a current of just 50 mA through the body can stop the heart.

An RCD does not replace a fuse. The fuse, nowadays usually a miniature circuit breaker (MCB), protects cables against overload and short circuit. The RCD protects people against dangerous residual currents. In the distribution board, the two work together.

Note: An RCD only trips if the residual current can actually flow away. TÜV Hessen points out that in some bathroom situations it does not trip, for example with an insulated bathtub. Electrical appliances should therefore be kept away from a filled bathtub.

Since when has the RCD been mandatory?

The RCD requirement has been extended over decades and always applies to installations newly built under the standard in force at the time. According to TÜV Hessen, the RCD has been mandatory in bathrooms of new buildings since 1984, and since 2007 for every newly installed socket-outlet circuit up to 20 A. Since October 2018, DIN VDE 0100-410 (the German standard for protection against electric shock) has also required it for lighting in dwellings.

RCD requirement in newly built installations (selection)
SinceScopeBasis
1984Rooms with a bathtub or shower in new buildingsDIN VDE 0100-701 (edition in force at the time)
2007Newly installed socket-outlet circuits up to 20 A, outdoors up to 32 ADIN VDE 0100-410:2007
2008Circuits in rooms with a bathtub or showerDIN VDE 0100-701:2008-10
October 2018Socket outlets up to 32 A for use by ordinary persons, outdoor socket outlets up to 32 A, lighting circuits in flats and single-family housesDIN VDE 0100-410:2018-10

For installations already being planned or built on 1 October 2018, a transition period until 7 July 2020 applied, according to the DKE (German Commission for Electrical, Electronic and Information Technologies). Since then, only the edition DIN VDE 0100-410:2018-10 applies to new installations.

Do I have to retrofit an older installation?

In an older installation in a private home, you do not have to retrofit an RCD merely because of its age. An installation that was correctly built to the rules of its year of construction may continue to be operated. According to TÜV Hessen, this protection of existing installations (Bestandsschutz) ends with certain alterations, changes of use or extensions, and when the installation evidently poses an immediate hazard.

For new socket outlets in an extended installation, DIN VDE 0100-410 requires an RCD of no more than 30 mA. Typical occasions are:

  • New socket outlets or a new circuit, for example in a converted loft
  • Bathroom renovation with a new electrical installation
  • A wallbox (EV charger), a heat pump or a PV system is added
  • Scorched cables, missing protective earth conductors or other visible damage

Even where it is not mandatory, an RCD increases safety in an older installation. Where modifying the distribution board is costly, the DKE permits RCD socket outlets, i.e. socket outlets with a built-in RCD, as an interim solution. This also applies to old installations with classic TN-C wiring (Nullung, combined neutral and protective conductor).

Which RCD type suits a wallbox and PV?

Under DIN VDE 0100-722, every charging point of a wallbox needs its own RCD of no more than 30 mA. According to the DKE, either a Type B is permitted, or a Type A or F combined with DC residual current monitoring to IEC 62955. If both are already built into the wallbox, this meets the requirement. The reason: devices with power electronics can generate residual currents that a simple RCD does not detect.

RCD types according to TÜV Hessen
TypeDetectsNote
ACsinusoidal AC residual currents onlyno longer approved for households since 1985; have it replaced if found
AAC residual currents and pulsating DC residual currents, but not smooth DC residual currentsusual type in homes and businesses
Fas Type A, plus mixed frequencies up to 1 kHzfor devices whose manufacturer requires it
Bas Type F, plus smooth DC residual currents (AC/DC sensitive)for applications where smooth DC residual currents may occur

For a PV system, battery storage or heat pump, the required RCD type is stated in the device manufacturer's documentation. For PV systems, the installation standard DIN VDE 0100-712 also applies. Both are checked before the distribution board is planned.

Is an arc fault detection device mandatory?

Under DIN VDE 0100-420:2022-06, an arc fault detection device is not a general requirement. In German it is often called a Brandschutzschalter; the technical term is arc fault detection device, AFDD for short. It detects arcs such as those that occur on damaged cables or loose terminals and disconnects the circuit. When planning new installations, however, a risk and safety assessment must be carried out and documented for these rooms:

  • Rooms used mainly for sleeping, such as bedrooms and children's rooms
  • Rooms or locations with a particular fire risk
  • Rooms made of combustible building materials with low fire resistance
  • Rooms containing irreplaceable goods, such as museums or archives

If the assessment identifies a particular risk, suitable measures are required. The AFDD is one of them; others are structural or organisational measures. According to the DKE, there is no general obligation to upgrade existing installations, but there is for alterations and extensions.

Note: As of October 2026: information based on DIN VDE 0100-420:2022-06 and the DKE FAQ list. The decisive edition is always the one in force when the installation is built or altered.

How often should you press the test button?

Press the test button of an RCD as specified by the manufacturer; in a private home without such a specification, roughly every six months. The button is usually marked T and simulates a residual current. This shows you whether the mechanism still trips.

For businesses, the implementation guidance to DGUV Vorschrift 3 (DGUV V3, the German statutory accident insurance regulation for electrical equipment) sets an interval for the test button of 6 months or every working day, depending on the area of use. Manufacturers may specify other intervals. For private homes there is no fixed interval; six months is a guideline there.

  1. Save any open work on your computer and switch off sensitive devices.
  2. Press the test button on the RCD.
  3. The lever must drop down immediately. The connected circuits are now de-energised.
  4. Switch the lever back up.
  5. If the RCD does not trip or cannot be switched back on, call a qualified electrical contractor.

Who may install an RCD?

Only a registered electrical contractor may install an RCD. The RCD sits in the distribution board and is therefore part of the fixed installation. Under § 13 of the Niederspannungsanschlussverordnung (NAV, the German Low Voltage Connection Ordinance), work on this installation may only be carried out by the grid operator or by installation companies listed in a grid operator's register of approved installers (Installateurverzeichnis).

Reinlicht Elektrotechnik is an electrical contractor based in Taufkirchen and is listed in the registers of approved installers of the grid operators in our service area. Before the retrofit, the on-site appointment establishes which earthing system is in place, whether every circuit has a protective earth conductor and whether there is room in the distribution board for one or more RCDs. After installation, the tripping current and tripping time are measured and recorded in a test report.

For the appointment, have ready what you know about the installation: approximate year of construction, existing documents and planned devices such as a wallbox, heat pump or PV system. If the measurement reveals defects in the older installation, you will learn about them before the work and can then decide whether only the RCD is added or the distribution board is renewed as well.

Frequently asked questions

The most common questions, answered briefly. If yours is not among them, call us or send an enquiry.

How can I tell whether I have an RCD?

Look in the distribution board: an RCD is usually wider than a single circuit breaker and has a test button marked T. The device shows the rated residual operating current, for protection of persons 30 mA or 0.03 A.

My RCD keeps tripping. Is it faulty?

Usually not. More often it is indicating a genuine fault in an appliance or in the installation. If it still trips when all plugs in the affected area are unplugged, a qualified contractor must locate the fault.

Is an RCD socket outlet enough instead of an RCD in the distribution board?

An RCD socket outlet only protects the devices plugged into it. It is suitable for individual rooms, such as a child's room. Only an RCD in the distribution board protects all circuits.

Do I need an additional RCD for a wallbox?

Whether a separate Type B is needed in the distribution board or the protection built into the wallbox is sufficient depends on the wallbox data sheet. A dedicated RCD per charging point is required in every case.

I have an old Type AC RCD. Does it have to go?

TÜV Hessen advises having a Type AC replaced if found, because it has not been approved for households since 1985. It only detects sinusoidal AC residual currents and misses pulsating DC residual currents, which a Type A detects.

What does retrofitting an RCD cost?

That depends on the condition of the distribution board, the number of circuits and the RCD type required. A qualified contractor can only quote a price after an on-site inspection.

Sources

Laws, standards and figures change. We checked the information as of the date given; the linked original sources are authoritative. This article does not replace advice on your specific case.

  1. TÜV Hessen (veröffentlicht vom VDE): Fehlerstromschutzeinrichtungen, Trügerische Sicherheit (opens in a new tab) accessed on 31 October 2026
  2. DKE: Erläuterungen zum Konzept von DIN VDE 0100-410 (VDE 0100-410):2018-10 (opens in a new tab) accessed on 30 October 2026
  3. DKE: Hinweise zum erleichterten Umgang mit DIN VDE 0100-410 (opens in a new tab) accessed on 30 October 2026
  4. DKE: FAQ-Liste zur Norm DIN VDE 0100-722 (VDE 0100-722):2019-06 (opens in a new tab) accessed on 30 October 2026
  5. DKE: FAQ-Liste zur Norm DIN VDE 0100-420 (VDE 0100-420):2022-06 (opens in a new tab) accessed on 30 October 2026
  6. DGUV, Fachbereich ETEM: Manuelle Funktionsprüfung von Fehlerstrom-Schutzeinrichtungen nach DGUV Vorschrift 3 (opens in a new tab) accessed on 31 October 2026
  7. Bundesministerium der Justiz: Niederspannungsanschlussverordnung (NAV), § 13 (opens in a new tab) accessed on 30 October 2026

Questions about your installation?

Call us or send an enquiry. We will assess the situation on site and tell you what is needed.