What are the employer's obligations?
Responsibility lies with the employer (Unternehmer), not with the inspector. Under § 5 of DGUV Vorschrift 3, the employer ensures that electrical installations and equipment are inspected for proper condition: before first commissioning, after an alteration or repair before being put back into service, and thereafter at specified intervals.
The Betriebssicherheitsverordnung (BetrSichV, German Ordinance on Industrial Safety and Health) sets out the same obligation from the perspective of occupational safety. Under § 14, the employer must have work equipment that is exposed to damaging influences inspected at regular intervals by a person qualified to carry out inspections. Under § 4(4), work equipment subject to inspection may only be used if the inspections have been carried out and documented.
- draw up the risk assessment and set the type, scope and intervals of the inspections in it
- select and appoint a suitable inspector, internal or external
- record and keep the inspection results
- have defects found remedied or take the affected equipment and parts of the installation out of service
Note: Even if a service provider carries out the inspection, the employer remains responsible for intervals and continued operation. This is stated in DGUV Information 203-071.
How are the risk assessment and inspection intervals linked?
There are no fixed statutory intervals for electrical inspections. Under § 3(6) of the Betriebssicherheitsverordnung, the employer determines the type, scope and intervals of the inspections. The intervals must be set so that the work equipment can be used safely until the next inspection.
DGUV Information 203-071 lists criteria for setting them, including:
- instructions from the manufacturer and installer
- conditions of use such as dust, moisture, oils, mechanical stress or harsh operation
- duration and frequency of use
- failure behaviour and results of previous inspections
- frequency and quality of maintenance
- qualifications and experience of the users
If the business lacks the expertise for this, the DGUV recommends expert support, for example from the inspector. If the business deviates from the guideline values in DGUV Vorschrift 3, the reasons are stated in the risk assessment.
Which inspection intervals apply to installations and equipment?
The implementation guidance to § 5 of DGUV Vorschrift 3 gives guideline values for normal operating and ambient conditions. It distinguishes fixed installations and equipment (Table 1A) from portable equipment (Table 1B), i.e. devices that are moved during operation or can easily be relocated.
| Installation or equipment | Interval | Inspected by |
|---|---|---|
| Electrical installations and fixed equipment | 4 years | Qualified electrician |
| Installations and fixed equipment in special locations and installations (DIN VDE 0100 Group 700) | 1 year | Qualified electrician |
| Residual current devices in fixed installations, test via test button | 6 months | User |
| Portable equipment, extension leads and connecting cables | Guideline 6 months, on construction sites 3 months | Qualified electrician; with suitable measuring equipment also an electrically instructed person |
| Maximum intervals if the failure rate is below 2 per cent | Construction sites, production and workshops 1 year, offices 2 years | as above |
The failure rate is the proportion of devices in an operating area that show defects during inspection. If it is no more than 2 per cent, the interval is considered adequate under DGUV Vorschrift 3 and may be extended up to the maximum values. According to DGUV Information 203-071, devices that already fail the visual inspection are included in the count.
Note: Fixed installations that are continuously maintained by qualified electricians and monitored by measuring systems, for example insulation monitoring, meet the inspection obligation under DGUV Vorschrift 3 even without periodic inspection. This does not apply to portable equipment.
Who may carry out the DGUV V3 inspection?
Under DGUV Vorschrift 3, responsibility for the inspection lies with a qualified electrician (Elektrofachkraft). For inspections under § 14 of the Betriebssicherheitsverordnung, this person must also be appointed as a person qualified to carry out inspections (befähigte Person). Under § 2(6), this is a person with suitable vocational training, professional experience and recent professional activity.
DGUV Information 203-071 adopts the requirements of TRBS 1203 (German Technical Rule for Operational Safety) for electrical hazards:
- completed vocational training in electrical engineering or a degree in electrical engineering
- at least one year of experience in installing, maintaining or inspecting electrical installations and equipment
- recent activity in this field
- up-to-date knowledge of the regulations, for example through training or exchange of experience
Under DGUV Vorschrift 3, electrically instructed persons may inspect portable equipment using suitable measuring and testing devices under the direction and supervision of a qualified electrician. DGUV Information 203-071 makes clear that they do not carry out inspections on their own responsibility but support the inspector within the inspection team. If you appoint a service provider, have the inspector's qualification confirmed in advance.
How does the inspection work while the business keeps running?
DGUV Information 203-071 recommends scheduling the inspections around operations and coordinating them with the users. No inspection may take place without a risk assessment for the inspection work itself, because inspecting also creates hazards for the inspector and the surroundings.
- Update the inventory of installations and equipment; have drawings and previous reports ready.
- Define the scope and dates of the inspection; split areas with machines, servers or cooling into sections.
- Brief the inspector on the site if they do not know it.
- Inspect visually, test and measure; record the results for each installation and device.
- Clearly mark failed devices as unsafe and withdraw them from use.
- Assess defects, have them remedied and adjust the intervals in the risk assessment.
For measurements on fixed installations, circuits are switched off one after another. Reinlicht Elektrotechnik is an electrical contractor based in Taufkirchen with a focus on industry and commerce, and inspects fixed installations and portable equipment under DGUV Vorschrift 3. We agree the procedure in advance with your maintenance or facility management team.
What belongs in the test report and documentation?
Under § 14(7) of the Betriebssicherheitsverordnung, the result of every inspection must be recorded and kept at least until the next inspection; electronic records are permitted. Mandatory details are the type, scope and result of the inspection, plus the name and signature of the inspecting person. DGUV Information 203-071 also recommends:
- unique identification of the installation or device, such as an inventory number or barcode
- reason for inspection: initial inspection, periodic inspection or inspection after repair
- standards applied, for example DIN VDE 0105-100 or DIN VDE 0701-0702
- measured values, test instrument used and next inspection date
- notes on continued operation: remedying defects, upgrading or taking out of service
The regulations do not generally require an inspection label. For equipment used at changing locations, however, the Betriebssicherheitsverordnung requires proof of inspection at the place of use; a label showing the inspection date and next due date meets this. At the request of the Berufsgenossenschaft (statutory accident insurance institution), the employer keeps an inspection log under § 5(3) of DGUV Vorschrift 3.
Note: Keeping measured values across several inspections lets you spot changes early and extend or shorten intervals with good reason.
What happens without an inspection?
Anyone who allows work equipment to be used without the required inspections having been carried out and documented commits an administrative offence under § 22(1) No. 8 of the Betriebssicherheitsverordnung. The same applies under No. 1 if the risk assessment is missing. Under its § 9, breaches of § 5 of DGUV Vorschrift 3 are an administrative offence under Book VII of the Social Code (Sozialgesetzbuch VII), punishable by a fine of up to ten thousand euros.
The consequences of a loss are usually more serious. Under § 81 of the Versicherungsvertragsgesetz (VVG, German Insurance Contract Act), an insurer may reduce its payment if the policyholder caused the damage through gross negligence. Property insurers may also set their own inspection intervals, as DGUV Information 203-071 notes. The terms of your policy are decisive.